|
5. CRYOCOOLER MAINTENANCE AND PROBLEMS:
The CTI manual on the cryocooler should be read carefully. This
is especially important regarding the tightening and removal of
the quick connect fittings on the pressure lines.
5-1 Replacement of the Charcoal Adsorber:
It is very important to replace the charcoal adsorber in the cryocooler
compressor every 1000 hours (once per year). New adsorbers are available
directly from CTI. This is the only routine maintenance that is
required on the cryocooler. Rebuilt adsorbers are also available
from Austin Scientific Company, but need to be ordered through 2G
Enterprises.
5-2. Cold head sticking noises:
A specific problem we have experienced is contamination in the cryocooler
system that results in sticking of the displacer in the cold head
component of the cryocooler. This sticking is evidenced by a stick-slip
noise from the cold head and can be observed visually by inspecting
the sight glass (if equipped) on the cold head. The rotating drive
mechanism will be erratic in phase with the sticking noise. It is
sometimes possible to remove the contaminant by purging the cold
head with the SRM at helium temperatures.
Please contact 2G before attempting to purge the cold head.
The following procedure MUST be carefully performed in the exact
sequence given.
We have developed a procedure that uses the cold head as a heat
engine, rather than a cooler, during the purge. To do a purge we
connect the cryocooler electrical drive power so that the cold head
runs in reverse direction. This causes the cold head to heat the
cryocooler cylinder and to warm the frozen contaminant so that it
is flushed out with the helium purge gas. The 2G cryocooler speed
control has two operating positions. One is for normal cooling operation,
and the second is for heating. The key switch is used to select
the desired operation. If the system is not fitted with a speed
control, then a special electrical adapter is available from 2G
to change the cold head direction. This adapter connects to the
compressor electrical connector marked "Cold Head Power"
and the cold head drive cable connects to the adapter. With this
adapter in line, the cold head will operate as a heat engine.
To purge the cold head:
5-2-1. Turn off the cold head and compressor and immediately disconnect
both pressure lines from the cold head. Cap the ends of the lines
and the fittings on the cold head. Let the system sit for at least
10 hours to warm the cold head.
5-2-2. Have a standard 210 cubic foot cylinder of 99.999% pure (ultra-high
purity) helium available and charged to at least 1500 psi. Use a
pressure regulator that has an output pressure of at least 270 psi.
Normal purity helium, such as that used for welding, is not pure
enough and will often cause further contamination during the purge
procedure.
5-2-3. Switch the speed control to HEAT or install the cold head
direction reversing adapter. If neither is available, the cryocooler
cable can be modified as described below to reverse the direction:
First, unplug the cable from the compressor. remove the 2 screws
and small clamp plates that secure the cable to the connector.
Put the connector back onto the compressor to hold it while unscrewing
the back of the connector (the part that the clamp screws went through).
This back part is a snug fit to the rubber sleeve around the wires
so try to hold the rubber sleeve to keep it from turning while you
unscrew the connector.
With the back of the connector slipped down on the electrical
cable you will see the wires that go to the cold head. Looking into
the front of the connector these wires are labeled A,B,C,D,E,and
F going clockwise from the alignment slot on the connector.
To reverse the motor direction you need to swap the 2 wires that
go to pins E and B (or D).
That is:
1. Remove the wire from pin E and remove the wire from pin B (it
may be on pin D)
2. Leave the jumper from pin B to D.
3. Connect the E wire to B and the B wire to E.
4. Leave the housing off for now, but protect the wires (and you)
from electrical shock with tape.
5. NOTE: It would be helpful to have a spare cable that is
modified for this reversed direction operation.
5-2-4. Have a 1/4 inch OD copper tube to connect the pressure regulator
to the 1/4 inch ÒGas ChargeÓ FLARE fitting on the compressor.
5-2-5. Connect the pressure regulator to the gas cylinder. Care
is required to prevent contamination of the gas in the cylinder
since the volume of the pressure regulator is filled with air which
will mix with the helium gas in the cylinder unless it is flushed
during the connection process. FIRST turn the regulator pressure
control in, i.e., so that gas flow will occur when pressure is supplied
to the input side. SECOND connect the regulator to the cylinder
then SLOWLY open the cylinder valve. A substantial flow of helium
gas must immediately pass through the regulator thereby flushing
the trapped air out rather than having it mix in the cylinder. After
about 10 seconds turn off the regulator control valve and open the
cylinder valve fully.
5-2-6. Connect the 1/4 inch copper tube to the regulator with fittings
adequate for the 270 psi charging pressure. Be certain that the
tube is long enough to reach the compressor input and then flush
the 1/4 inch tube with helium gas through the regulator for about
60 seconds. While gas is still flowing out the tube connect it to
the compressor. Before fully tightening the fitting at the compressor
open the compressor gas charge valve to let a small amount of helium
from the compressor flush out the section of line between the valve
and the fitting. Now tighten the connection and then increase the
pressure on the regulator to 250 psig.
5-2-7. Attach the purge valve supplied with the cryocooler tool
kit to the cold head SUPPLY fitting. Tighten only a few turns at
this time, and be certain that gas does not flow out the purge valve.
5-2-8. Open the compressor charge valve and simultaneously turn
on the compressor and connect the SUPPLY line to the cold head RETURN
fitting AND turn on the cold head drive. These three operations
are to be done in the order given and in rapid succession, but don't
panic. Adjust the pressure regulator to keep the compressor pressure
at 250 psig.
5-2-9 Now, carefully tighten the purge valve on the SUPPLY fitting,
by hand, until gas flows out the valve. The objective is to get
a good flow on the compression stroke, and still maintain some flow
at all times. If the valve is tightened too much the compression
stroke will give a burst of gas but then the flow will stop completely,
making it possible for air to be drawn into the cold head. Continue
to run the system as connected until about 1500 psi pressure drop
occurs in the helium gas supply cylinder. Be certain to leave about
500 psig in the gas supply cylinder
5-2-10. The cold head should run smoothly without any stick-slip
sounds.
5-2-11. To STOP PURGE, remove the purge valve and simultaneously
turn off the compressor. Reconnect the supply line to the SUPPLY
fitting on the cold head, and the return line to the RETURN fitting
on the cold head. Switch the speed control to COOL or remove the
direction reversing adapter from the cold head drive circuit. Restart
the compressor and after running for a few minutes add helium gas
to achieve a compressor pressure of about 280 psig. Close the compressor
charge input valve, reduce the pressure regulator pressure to zero
and remove the charge line.
5-2-12. This should have cleared the cold head of contaminants.
It will now require about 24 hours for the SRM to return to equilibrium
temperature and operation.
5-3. CHANGING THE COLD HEAD: The cold head
may need to be changed if the above procedures do not solve the
sticking problems. This may be done with the magnetometer at helium
temperatures, or when the system is warmed to room temperature.
5-3-1: Cold exchange of the cold head: This procedure requires special
tools and fixtures and should be done by a certified Cryogenic Technology
Inc. (CTI) engineer or by a 2G engineer. Please contact CTI and
2G before this is done. Note, that the cold head cylinder is
a permanent part of the 2G helium dewar and is not to be removed
with the cold head. To do an exchange, only the displacer part of
the cold head is removed. Any loosening of the 10-32 bolts that
hold the CTI cylinder to the 2G vacuum jacket can result in loss
of dewar high vacuum and create a very dangerous and damaging situation.
Back to top | Back
to Maintenance
|